Configure Ac-Powered Sensors Using Browser-Based Configuration - Primex Wireless SNS2TPS-2 Installation Manual

Temperature and humidity sensors
Table of Contents

Advertisement

Configure Sensors for the Network
4. On the General tab under "This connection uses the following items" list, select the Internet
Protocol (TCP/IP) item, and then click the Properties button. You will see the Internet
Protocol (TCP/IP) dialog box, as shown in Figure 17.
the Use the following IP address option button, and enter the following
5. Choose
informat
ion:
In the IP address field, enter 192.168.1.100.
In the Subnet Mask field, enter 255.255.255.0.
6. Click the OK button to accept the IP address changes and return to the Local Area
Connection Properties dialog box.
7. Again, click the OK button to accept the changes, close the dialog box, and return to the
Network Connections window.
8. Close the Network Connections window.
You are now ready to physically connect the AC-powered sensor device to the computer for
browser-based configuration.

Configure AC-powered Sensors using Browser-based Configuration

In the event that you cannot connect the sensor to the network on the same subnet as the AMP, for
example, if you are configuring sensors for use in a newly constructed building without a network, or
you are configuring the sensors at a maintenance facility not on the network, you can use Browser-
based Configuration to configure AC-powered sensors. When a sensor is configured using
Browser-based Configuration, you connect the sensor to a laptop and use the sensor's web server
to enter information for the sensor to connect to the SNS AMP. Later, when the network is available
and the AMP is installed, you connect the sensor to the network and force it to check in with the
AMP.
Primex Wireless, Inc.
Configure AC-powered Sensors using Browser-based Configuration
Figure 17: Internet Protocol (TCP/IP) Properties