PROGRAMMING

NT538 WS

STEP
PRESS
Keep the PRG key pressed until the display shows PRG
1
Select PRG SET for entering in the programming mode
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
EFFECT
SET
or PRG 1 to restore the default programmed value.
The display shows CH1
Enabling CH1
Select YES or NO
The ALARM CH1 threshold for is displayed
Set the desired threshold, the Alarm LED flashes
Set the desired threshold
The TRIP threshold appears for CH1
the led Trip flashes.
Set the desired threshold
The display shows CH1 FAN YES
the Fan1-2 LEDs flash.
Select: YES FAN1+FAN2 enabled flashing
YES only FAN1 enabled flashing
YES only FAN2 enabled flashing
NO led FAN1- FAN2 off
Repeat the steps listed above for all the channels
CH2-CH8.
The display shows ON
the LED FAN1 flashes
Set the desired threshold FAN1 ON
The display shows OFF
the LED FAN1 flashes
Set the desired threshold FAN1 OFF
The display shows ON
the LED FAN2 flashes
Set the desired threshold FAN2 ON
The display shows OFF
the LED FAN2 flashes
Set the desired threshold FAN2 OFF
NT538 WS
PRESS
NOTES
PRG 1 default data
with YES the CH1 is
enabled
with NO the CH1 is
disabled
Default 90°C
Default 119°C
info fan operation:
paragraph fan command
page 17
Default YES FAN1+FAN2
Default 70°C
Default 60°C
Default 45°C
Default 35°C