ABB LMT Series Operating Instruction page 51

Magnetostrictive level transmitters foundation fieldbus
Hide thumbs Also See for LMT Series:
Table of Contents

Advertisement

L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A
STEP 3:
Press
or
to navigate to the Calibrate menu
Press Select
to enter the menu
STEP 4:
Press
or
to navigate to the Level Calibration
menu
Press Select
to enter the menu
IMPORTANT (NOTE)
Calibration points menu description
1 Sensor Value label
2 Current sensor value is the raw factory level being measured
currently
3 Calibration point index (options 00 and 01)
4 Level value (LVL) or output value of the cal point
5 Sensor value (SVL) or input value of the cal point
• The scroll function accessed by pressing the
navigation between the point number "00", the Input Value
<In>, and the Output Value <Out>
• To change between points, press
highlighted or
when "01" is highlighted
• To edit the input or output value of the points press the
key when <In> or <Out> are highlighted respectively
STEP 5:
Press
value of point 00
For wet calibration, the float must be at the position where the
cal Point 00 is wanted
For dry calibration, skip to Step 6
Press
input value of the point
STEP 6:
For dry calibration, when the float or level cannot be moved to
the desired position for point 00, press <right> to edit the
input value
Press
Press
Press
STEP 7:
Press
Press
as in Step 6 to edit the digits
key allows
when "00" is
to scroll to <In>, which corresponds to the input
to capture the Current SVL and apply it to the
to scroll from one digit to another
and
to edit each digit
to confirm the input value
to scroll to <Out>
to edit the output value Follow the same procedure