L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A
Figure 22 Remote version: connecting the signal cable
Terminal
Color / function
VDD
Yellow
/M/R
White
GND
Green
HS
Pink
DX
Gray
RX
Brown
Ground terminal (functional ground / shield)
NOTICE
The shielding of the signal cable also serves as a functional
ground and must be connected to the sensor and to the
transmitter on both sides
1 Use the signal cable connected to the transmitter to make
the electrical connection between the measuring sensor and
the transmitter
2 Unscrew the cover of the terminal boxes on the transmitter
and the measuring sensor
3 Tailor the signal cable in accordance with specification
4 Insert the cable through the cable gland into the terminal
box
5 Tighten the cable gland
6 Connect the wires to the corresponding terminals (refer
figure 22)
7 Connect the shield of the signal cable to the forked cable lug
to the ground terminal
8 Screw on the cover of the terminal compartment on the
transmitter and the measuring sensor and tighten by hand
Make sure the gaskets for the cover are seated properly
23