Vacon NXI FI9 series User Manual page 80

Table of Contents

Advertisement

80
vacon
Fault
Fault
code
35
Application
36
Control unit
37
Device changed
(same type)
38
Device added
(same type)
39
Device
removed
40
Device
unknown
S1 = Unknown
device
S2 = Power1
not same type
as Power2
41
IGBT
temperature
42
Internal brake
resistor
overtemperature
43
Encoder fault
1 = Encoder 1
channel A is
missing
2 = Encoder 1
channel B is
missing
3 = Both
encoder 1
channels are
missing
4 = Encoder
reversed
5 = Encoder
board missing
7
Possible cause
Problem in application software.
Software function requires newer
control board.
Option board or control unit changed.
Same type of board or same power
rating of drive. The parameters are
available in the drive.
Option board or drive added.
Drive of same power rating or same
type of board added. The parameters
are available in the drive.
Option board removed.
Drive removed.
Unknown option board or drive.
IGBT Inverter Bridge overtemperature
protection has detected too high a
short term overload current
Internal brake resistor
overtemperature protection has
detected too heavy braking
Note the exceptional Fault data
record. See 7.3.4.3. Additional codes:
1 = Encoder 1 channel A is missing
2 = Encoder 1 channel B is missing
3 = Both encoder 1 channels are
missing
4 = Encoder reversed
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
control keypad
Correcting measures
Contact the nearest distributor.
For local contacts, go to:
http://drives.danfoss.com/danfoss-
drives/local-contacts/
If you are an application
programmer, check the application
program.
Change control unit
Reset. The device is ready for use.
The drive starts to use the old
parameter settings.
Note: No fault time data record!
Reset The device is ready for use.
The drive starts to use the old
parameter settings.
Note: No fault time data record!
The device is not available. Reset
Note: No fault time data record!
Contact the nearest distributor.
For local contacts, go to:
http://drives.danfoss.com/danfoss-
drives/local-contacts/
Check loading.
Check motor size.
Make an identification run.
Set the deceleration time longer.
Use external brake resistor.
Check encoder channel connections.
Check the encoder board.
Check the encoder frequency in the
open loop.