technical data
Figure 4-2. Low overload
The high overload means that if 150% of the continuous current (IH) is required for 1 minute
every 10 minutes, the remaining 9 minutes must be approximately 92% of IH or less. This is
to make sure that the output current is not more than IH during the duty cycle.
Figure 4-3. High overload
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
vacon
19