In the event of a fire, evacuate the building or equipment site and raise the fire
alarm at the closest alarm point, or call the emergency number. Do not re-enter
a burning building under any circumstances.
Heater in operation. Do not block the heater vents or place combustible
materials close to the unit, as this can cause a fire that can endanger life.
2.6.1
Fire Precautions
Note: When working with the installation or maintenance of equipment that
Fire can spread to neighboring rooms. When working on equipment cable
ducts, channels and access holes might have to be opened, thereby interfering
with the fire sectioning of the building. The instructions below have to be
followed when work has been completed to restore the building's fire sectioning:
1. Close the cable ducts and fire doors (if applicable) as soon as possible.
2. Seal cable ducts according to the regulations for the building.
3. Minimize the amount of inflammable material.
4. Remove empty packaging material from the equipment site.
5. Check that there is a functioning powder or carbon dioxide fire extinguisher
2.7
Heat Hazards
This section describes how to avoid injury from hot surfaces or hot air in
equipment.
EN/LZT 720 0027 Uen R8A 2006-06-27
involves interfering with the fire sectioning of a building, this should be
carried out as quickly as possible.
for electric apparatus at the equipment site.
RBS 2308 and RBS 2309 User's Guide