Technical data of CPU 31xC
6.6 Technical data of the integrated I/O
Technical data
Current consumption
with load voltage L+
Status, interrupts, diagnostics
Status display
Interrupts
Diagnostics functions
Data for the selection of an actuator for
standard DI
Output voltage
For signal "1"
Output current
For signal "1"
Rated value
Permitted range
For signal "0" (residual current)
Load impedance range
Lamp load
Parallel connection of 2 outputs
for redundant load control
for performance increase
Controlling of digital inputs
Switching frequency
under resistive load
For inductive load to IEC 947-5, DC13
under lamp load
fast outputs under resistive load
Inductive breaking voltage limited internally to
Short-circuit protection of the output
Response threshold
6-48
CPU 312C
CPU 313C
Max. 50 mA
Max. 100 mA
CPU 312C
CPU 313C
green LED per channel
no interrupts when operated as standard I/O
For using technological functions, please refer to the
Functions
Manual.
no diagnostics when operated as standard I/O
For using technological functions, please refer to the
Functions
Manual.
CPU 312C
CPU 313C
Min. L+ (-0.8 V)
0,5 A
5 mA to 600 mA
Max. 0.5 mA
48 Ω to 4 kΩ
Max. 5 W
Supported
Not possible
Supported
Max. 100 Hz
Max. 0.5 Hz
Max. 100 Hz
Max. 2.5 kHz
Typically (L+) - 48 V
Yes, electronic
Typically 1 A
CPU 313C-2
CPU 314C-2
Max. 100 mA
Max. 100 mA
CPU 313C-2
CPU 314C-2
Technological
Technological
CPU 313C-2
CPU 314C-2
CPU 31xC and CPU 31x, Technical Data
Manual, 01/2006 Edition, A5E00105475-06