d16 Fan activation delay at controller start-up and defrost-end: This parameter
sets the time interval that starts at controller start-up or at the end of a defrost cycle,
during which the fan must remain off in order to not introduce warm and humid air
into the case or coldroom (only for model ICON-132S & ICON-132SR). At the end of
this time interval the fan will be activated when the defrost termination temperature
drops and reaches the value set in parameter d17.
d17 Fan activation temperature at controller startup and defrost-end: This
parameter sets the defrost termination temperature value, detected by the defrost-
termination temperature probe, and below which the fan will be activated when the
time set in parameter d16 ends (only for model ICON-132S & ICON-132SR).
d19 Display Offset: This parameter fixes the positive or negative correction applied
to the value detected by the temperature probe and the value shown in the display.
d20
Probe
Type
Selection:
Where 0= PT1000 and 1= 2k NTC.
d22 Unit of measure: This parameter fixes the unit of measure regarding the
o
temperature, i.e.,
C if d22=0 or
d23 Compressor function during a probe failure: This parameter fixes the
compressor operating mode during a temperature probe failure. If d23=0, the
compressor is deactivated and remains that way until the failure is repaired. If
d23=1, the compressor is activated and remains that way until the failure is repaired.
Whenever a failure occurs, if d23=2, the compressor alternates a time interval set in
parameter d25, during which it remains deactivated, with a time interval set in
parameter d24, during which it remains activated and so on.
d24 Compressor ON-time during a probe failure: This parameter sets the time
interval. That alternates with the time interval set in parameter d25, during which the
compressor must remain activated during a probe failure and if parameter d23=2.
d25 Compressor OFF-time during a probe failure: This parameter sets the time
interval, that alternates with the time interval set in parameter d24. During which the
compressor must remain deactivated during a probe failure and if parameter d23=2.
d26 Defrost control via real-time clock or Genus
for stand-alone controller via real-time clock or remote defrost control for networked
controller when connected to Genus
d27 Stub number: number given to identify refrigeration stub from 0...99 when
connected to, and viewed from, a Genus
d28 Case number: number given to identify refrigeration case from 0...9...A...U
when connected to, and viewed from, Genus
®
d29
Connect to Genus
®
connection to a Genus
front end.
d30 Defrost cycle 1 start time: This parameter sets the time for the first defrost
cycle within a 24 hour period.
d31 Defrost cycle 2 start time: This parameter sets the time for the second defrost
cycle within a 24 hour period.
d32 Defrost cycle 3 start time: This parameter sets the time for the third defrost
cycle within a 24 hour period.
d33 Defrost cycle 4 start time: This parameter sets the time for the fourth defrost
cycle within a 24 hour period.
d34 First defrost cycle after controller startup: This parameter fixes the time
interval, starting at controller startup, after which the first defrost cycle is activated. If
d34=0, the first defrost cycle starts 10 minutes after controller startup. If d34=1, the
first defrost cycle starts after the hours set in d8.
d38 Minimum temperature alarm differential: This parameter sets the
temperature below the set point (d1) which activates an under-temperature alarm,
subject to the alarm delay d7.