Cables; Contactors, Dc Bus And Brake Circuit; Ready Signals - ABB ACS850 Application Manual

Common dc configuration
Hide thumbs Also See for ACS850:
Table of Contents

Advertisement

Cables

• Select the input power cables as described in the appropriate drive Hardware Manual.
The cross-sectional area of the DC cables must be the same as the cross-sectional
area of the AC side cables.
• If screened DC cables are used, ground the screen at the other end only.
• The lengths of the supply cables must not differ more than 15%. This applies
especially to converters equipped with DC chokes.
• Maximum length of the DC cables between two converters is 50 m.
• If the system consists of more than two converters, the DC links must be connected in
an external terminal box. Do not use the terminals of one of the converters for this
purpose.

Contactors, DC bus and brake circuit

If converters with different charging circuits are connected directly to the main supply,
the DC links must be connected together via contactors. With an external or an internal
brake chopper a contactor must be used for protection against brake chopper faults.
• Contactors must be capable of cutting off the DC current. The maximum
operational voltage over the contactor is the DC voltage during the braking, i.e. 1.21 ·
1.35 · U
.
1
• DC current rating for the DC contactor can be calculated by as follows:
is the drive power rating of the biggest converter and U
P
cont.max
the converter.
I
= P
/U
DC
DC
DC
≈ P
P
DC
cont.max
U
= 1.35U
DC
1
Peak current through the contactor in brake resistor circuit can be calculated as
follows:
I ˆ=(1.21U
) /R
brake
DC
The rms current during the braking can be calculated as follows:
½
I
=(P
/R
)
rms
br
brake
is the brake resistor's resistance. P
R
brake

READY signals

To ensure that all of the DC links have been charged before the system is started, the
READY signals of the converters must be wired together. If this is neglected, the
charging resistor can be damaged.
Wire together the READY signals of all the converters connected to the main supply
and the START INTERLOCK signals of all of the converters not connected to the main
supply. An example is presented below.
is the applied braking
br
Common DC configurations
is the supply voltage of
1
power.