Frame Sizes A; Frame Sizes E0, E And G; Supply Units Other Than Acs850; Mains Choke Selection - ABB ACS850 Application Manual

Common dc configuration
Hide thumbs Also See for ACS850:
Table of Contents

Advertisement

The peak current during charging is calculated by the equation in
charging
Charging time is longer if a higher resistance value is used.
It must be checked that AC supply side components can withstand the peak current.
Charging resistor energy withstand is calculated by equation E = 1.3CU
total capacitance of DC-link capacitors and U is supply line-to-line rms voltage for
example 400 V or 500 V. The factor 1.3 covers the upper tolerance limit of
capacitance.
If drive units with different charging circuits are used, the DC-links must be connected
together via contactors.
Frame sizes A...D
If only frames A...D are used, there is no need for an external charging circuit with the
external DC supply, because the drive modules have internal charging circuits in series
with DC-link capacitors.

Frame sizes E0, E and G

In frame sizes E0, E and G, the charging circuit is in parallel with the input bridge.
Separate charging circuit is needed.
The AC fan of ACS850 frame G must be powered separately. See chapter
the AC fan in frame

Supply units other than ACS850

When some other type of supply unit than ACS850 is used, its DC voltage compatibility
with the drive units must be checked in addition to the earlier described items (see
section

Mains choke selection

In common DC connections, the drive module(s) connected to the AC supply must be
equipped with mains choke(s). The mains chokes are needed:
to get the maximum DC power ratings from the drive module(s)
to reduce the AC input current (rms, peak) level
to meet the requirements for harmonic distortion
to balance the supply current in a multiple AC input.
capacity.
G.
DC voltage
limits).
Checking the
2
where C is
Powering
Common DC configurations
25