ABS lifting station Nirolift
ABS lifting station Sanisett
Installation and Operating Instructions
GB
www.absgroup.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Sanisett and is the answer not in the manual?

Questions and answers

Summary of Contents for ABS Sanisett

  • Page 1 ABS lifting station Nirolift ABS lifting station Sanisett Installation and Operating Instructions www.absgroup.com...
  • Page 2: Table Of Contents

    Installation of the control unit ........................8 Commissioning ............................. 8 Maintenance ............................9 Commentary on maintenance of lifting stations in accordance with EN 12056 ........9 General maintenance hints ........................9 ABS reserves the right to alter specifications due to technical developments...
  • Page 3: General

    General 1.1 Application areas Synthetic-prefabricated, corrosion resistant sump for ABS submersible pumps designed as single pumping station for automatic pumping of wastewater and sewage in accordance with DIN/EN 12056 from locations and areas below the backwash level. These lifting stations may not be used for the collection or pumping of flammable or corrosive liquids.
  • Page 4 Installation and Operating Instructions ABS lifting station Nirolift & Sanisett Figure 2 Sanisett installation example and dimensions Figure 3 Opening connection ports Figure 4 Sanisett float switch installation Figure 5 Mounting of upper fitting Figure 6 Sanisett above ground lid...
  • Page 5: Commentary On The Legal Regulations Covering The Use Of Lifting Stations For The Pumping Of Faecal Free Effluent

    The Sanisett is also supplied with a junction piece for the discharge line and a bracket for the level control. The collection tank is supplied as standard with a number of closed off inlet ports. The inlet ports DN 100 Nirolift and DN 100/150 Sanisett can be opened as required (See Figure 3).
  • Page 6: Set-Up And Installation

    Set the collection tank on a bed of sand in the prepared opening of dimensions approximately 600x600x750mm Nirolift and 1100x900x850 mm Sanisett in a frost free area and ensure that it is horizontal in all directions. Place the tank in such a manner that the vent openings are in line with the chosen pipe directions.
  • Page 7: Opening Of The Collection Tank Inlet Ports

    Installation and Operating Instructions ABS lifting station Nirolift & Sanisett ABS lifting station Nirolift & Sanisett 4.3 Opening of the collection tank inlet ports Only open inlet ports that are to be used. Only saw off as little as possible so that as much neck as possible is left for the plug connection. (Note the notch on the port neck).
  • Page 8: Level Control

    ABS lifting station Nirolift & Sanisett 4. Level control The float switches required for the twin unit Sanisett should be fitted into the collection tank at the correct level setting. (See Figure 4) NOTE Press the float switch cable into the plastic swivel in the holding bracket at distance of 15 mm between the float switch housing and swivel.
  • Page 9: Maintenance

    Lubricated-for-life ball bearings together with monitoring devices ensure optimum pump reliability provided that the pump has been connected and operated in accordance with the operating instructions. Should, nevertheless, a malfunction occur, do not improvise but ask your ABS customer service department for assistance.
  • Page 10 ABS Production Wexford Ltd., Clonard Road, Wexford, Ireland Tel. +353 53 91 63 200 Fax +353 53 91 42335. www.absgroup.com...