Factory Page Parameter Table
P a ra m e te r
D e s c rip tio n
St or e 1.000V ca libr a t ion
for t h e pr ocess ou t pu t .
St or e 10.000V ca libr a t ion
for pr ocess ou t pu t .
Main > Factory > Calibration >
Rest or es or igin a l fa ct or y
ca libr a t ion
va lu es.
✔ N o te : F or m or e in for m a t ion a bou t h ow pa r a m et er set t in gs a ffect t h e
con t r oller 's oper a t ion , see t h e F ea t u r es Ch a pt er.
Watlow Series F4P
Ra n g e
(Mo d bu s Va lu e )
0.000 t o 3.000V
(0 t o 3000)
0.000 t o 12.000V
(0 t o 12000)
In pu t 1 (0)
In pu t 2 (1)
In pu t 3 (2)
Mo d bu s
Re g is te r
re a d /w rite
D e fa u lt
(I/O, S e t)
1.000V
Ou t pu t
1606
[1A]
1611
[1B]
Rexm it
1626
[1]
1631
[2]
r /w
10.000V
Ou t pu t
1607
[1A]
1612
[1B]
Rexm it
1627
[1]
1632
[2]
r /w
1601
wr it e on ly
Co n d itio n s fo r
P a ra m e te rs to Ap p e a r
Act ive: Alwa ys.
Act ive: Alwa ys.
Act ive: Alwa ys.
In pu t s 2 a n d 3 a ppea r on ly if t h e
con t r oller is t h e en h a n ced ver -
sion (F 4P _ - _ _ AB - _ _ _ _).