System Bus Wiring (Can) - Lenze EPM-H315 Operating Instructions Manual

Hide thumbs Also See for EPM-H315:
Table of Contents

Advertisement

Available languages

Available languages

Show/Hide Bookmarks
Installation
3.2.2

System bus wiring (CAN)

Schmatic diagram
A
Bus device 1
1
Only connect terminals of the same signal type.
Features of the signal cable:
Total cable length
Cab e type
Cable type
Cable resistance
Capacitance per unit length
Connection of bus terminating resistors:
One 120 Ω resistor at both the first and last bus device
Features:
CAN-based with bus protocol to CANopen (CAL-based communication profile DS301)
Bus length:
– 25 m at max. 1 Mbit/s data transfer rate
– up to 1 km at reduced data transfer rate
Very reliable data transfer (Hamming distance = 6)
Signal level to ISO 11898
Up to 63 bus participants possible
40
A
(H315)
1
-V
CAN-
Shield
CAN+ N.C.
120
A
2
up to 300 m
LIYCY 2 x 2 x 0.5 mm
twisted in pairs with shielding
Pair 1: CAN-LOW (LO) and CAN-HIGH (HI)
Pair 2: 2 GND
≤ 40 Ω /km
≤ 130 nF/km
EDBEPM-H315 DE/EN/FR 2.0
A
2
CG LO HI
CG LO HI
Bus device 2
2
A
n
CG LO HI
CG LO
HI
120
H315_004
A
Bus device n
n
300 to 1000 m
2
CYPIMF 2 x 2 x 0.5 mm
≤ 40 Ω /km
≤ 60 nF/km
L

Advertisement

Table of Contents
loading

Table of Contents