Conversion Setting For Disconnection Detection (Un\G164, Un\G165) (Q68Td-G-H02 Only) - Mitsubishi Melsec-Q Series User Manual

Channel isolated thermocouple input module. gx configurator-ti
Hide thumbs Also See for Melsec-Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
3.4.25
When disconnection is detected, a value stored into CH
(Un\G11toUn\G18) is set. (Refer to Section 3.2.2)
The value to be stored is selected from "Up scale", "Down scale" or "Given value".
(1) Setting methods
Un\G164 (Conversion setting for
disconnection detection CH1-4)
Un\G165 (Conversion setting for
disconnection detection CH5-8)
Figure 3.38 Setting of Conversion setting for disconnection detection (Un\G164, Un\G165)
(2) Default value
3
- 56
3.4 Buffer Memory

3.4.25 Conversion setting for disconnection detection (Un\G164, Un\G165) (Q68TD-G-H02 only)

Conversion setting for disconnection detection (Un\G164,
Un\G165) (Q68TD-G-H02 only)
(a) Set the value to be stored into buffer memory.
b15
to
CH4
CH8
The value to be stored into CH
changes as follows, depending on the setting value.
1) Up scale (0
)
H
Up-scale of the range currently set is stored.
2) Down scale (1
H
Down-scale of the range currently set is stored.
3) Given value (2
H
The value set in CH
(Un\G166toUn\G173) is stored.
(b) Turn on Operating condition setting request (Y9) to activate the setting.
All channels are set to "Down scale" (1111
POINT
If a value out of the setting range is set, the module operates with the default
setting, "Down scale"(1
b12 b11
to
b8 b7
CH3
CH7
Measured temperature value at the
time of disconnection detection
Measured temperature value (Un\G11toUn\G18)
)
)
Conversion setting value for disconnection detection
).
H
).
H
Measured temperature value
to
b4 b3
to
CH2
CH1
CH6
CH5
Setting
value
Up scale
0
H
Down scale
1
H
Given value
2
H
b0