Ch[ ] Time/Count/Moving Average/Time Constant Setting (Un\G1 To Un\G8) - Mitsubishi Melsec-Q Series User Manual

Channel isolated thermocouple input module. gx configurator-ti
Hide thumbs Also See for Melsec-Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
3.4.3
When the averaging processing (1
selection (Un\G24, Un\G25), time average, count average, moving average or time
constant for primary delay filter is set. (Refer to Section 3.2.1)
(1) Setting methods
(2) Default value
3
- 36
3.4 Buffer Memory

3.4.3 CH[ ] Time/Count/Moving average/Time constant setting (Un\G1 to Un\G8)

CH[ ] Time/Count/Moving average/Time constant setting (Un\G1 to
Un\G8)
(a) Set the following setting range in buffer memory.
Table 3.10 Settable range
Processing method
Time average
Count average
Moving average
Primary delay filter
* 1 Set the values in units of 320ms.
For the details of the setting values, refer to Section 3.2.1 (3) Averaging processing or Section
3.2.1 (4) Primary delay filter.
(b) Turn on Operating condition setting request (Y9) to activate the setting. (Refer to
Section 3.3.2)
All channels are set to "0".
POINT
(1) When a value out of the setting range in Table 3.10 is written, an error occurs
and the following also occurs.
• The error codes (20 , 30 , 31 , 32 ) are stored to the error code
(Un\G19). (Refer to Section 8.1)
• Error flag (XF) turns on.
• Conversion processing is performed with the setting before the error
occurence.
(2) When a value is set on the channels set sampling processing (0
Averaging processing selection (Un\G24, Un\G25), the setting value of CH
Time/Count/Moving average/Time constant setting (Un\G1 to Un\G8) is
ignored.
to 4
) is specified with Averaging processing
H
H
Setting value
*1
1280 to 5000(ms)
4 to 500(times)
2 to 60(times)
*1
320 to 5000(ms)
) to
H