Disconnection State Conversion Setting Function (Q68Td-G-H01 Only) - Mitsubishi Melsec-Q Series User Manual

Channel isolated thermocouple input module. gx configurator-ti
Hide thumbs Also See for Melsec-Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
3.2.3
Disconnection state conversion setting function (Q68TD-G-H01
only)
This disconnection state conversion setting function stores specific values into measured
temperature values when disconnection is checked.
This function can identify the disconnection detection from measured temperature values.
This function is only available for channels enable temperature conversion.
(1) Overview of disconnection monitor
CH
(a) It takes up to 11s from when line is disconnected till when disconnection is
(b) When disconnection is checked, the value selected from "Up scale", "Down scale"
(c) After disconnection state is restored, the batch-update of measured temperature
(d) The state of Disconnection state monitor flag (Un\G49), Disconnection state
(e) For operating the warning output function in disconnection and restoration, refer
Normal
Disconnection state
monitor signal (XC)
Disconnection state monitor
flag (Un\G49)
Measured temperature value
Measured
temperature
(Un\G11 to Un\G18)
value
Error clear request (YF)
Figure 3.7 Overview of disconnection monitor
monitored.
The measured temperature value decreases till when disconnection state is
checked.
When disconnection is checked, Disconnection state monitor flag (Un\G49) and
Disconnection state monitor signal (XC) turn on. Consequently, "ALM" LED blinks.
or "Given value" in Disconnection state conversion setting (Un\G164,Un\G165) is
stored into the CH
Measured temperature value (Un\G11 to Un\G18).
The values specified in Disconnection state conversion setting
(Un\G164,Un\G165) remains from when disconnection state is restored till when
normal measured temperature value is stored.
value restarts automatically.
It takes up to 11s from when disconnection state is restored till when measured
temperature value is stored into CH
Un\G18).
signal (XC), and "ALM" LED remains, which means the state of disconnection
detection, remains even when disconnection state is restored. Turn on Error clear
request (YF).
to Section 3.2.4.

3.2.3 Disconnection state conversion setting function (Q68TD-G-H01 only)

Maximum 11s
Maximum 11s
Disconnected
Normal
Normal(0)
Disconnected(1)
Measured
Conversion setting for
temperature value (in
disconnection state value
a gradual decline)
Measured temperature value (Un\G11 to