Offset/Gain Setting Mode (Un\G26,Un\G27) - Mitsubishi Melsec-Q Series User Manual

Channel isolated thermocouple input module. gx configurator-ti
Hide thumbs Also See for Melsec-Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
3.4.10

Offset/gain setting mode (Un\G26,Un\G27)

A channel targeted for adjusting offset/gain setting values in the offset/gain setting mode is
specified. (Refer to Section 4.6)
(1) Setting methods
Set a channel targeted for adjusting offset setting in Un\G26, and a channel for gain
setting in Un\G27.
Un\G26
(Offset specification)
Un\G27
(Gain specification)
Figure 3.29 Setting of Averaging processing selection (Un\G24,Un\G25)
(2) Default value
All channels are set to "Disable" (0000
POINT
b15 b14 b13 b12 b11
0
0
0
0
0
0
0
0
0
0
Data for b8 to b15 are fixed to "0".
Setting multiple channels at the same time is possible, however, set offset and
gain values separately (set "0" in either Un\G26 or Un\G27).
When both values are set at the same time, an error (error code: 500) occurs.
3.4.10 Offset/gain setting mode (Un\G26,Un\G27)
b10
b9
b8
b7
b6
b5
0
0
0
CH8 CH7 CH6 CH5
0
0
0
CH8 CH7 CH6 CH5
).
H
3.4 Buffer Memory
b4
b3
b2
b1
b0
CH4 CH3 CH2 CH1
CH4 CH3 CH2 CH1
1: Setting channel
0: disable
3
- 41
1
2
3
4
5
6
7
8

Advertisement