SECTION 4 - GENERATOR SPECIFICATIONS
Models
Rated Maximum Power and
Load Current (LP)
at 240 Volts
Rated AC Voltage
Rated Frequency
Phase
Rated Temperature
Normal Operating Range
LP Fuel Supply Pressure
LP Fuel Supply Consumption
NG Fuel Supply Pressure
NG Fuel Consumption
RESISTANCE VALUES
Rotor
Power Winding
Excitation Winding
FASTENER TORQUE VALUES
Engine Adapter to Engine
Alternator Adapter to Engine Adapter
Rotor Bolt to Crankshaft
Brushes to Rear Bearing Carrier
Stator Bolt
Negative Battery Cable to Engine
Muffler to Cylinder Head
at 1/2 Load
at Full Load
at 1/2 Load
at Full Load
c= Cubic Feet Per Hour
b= BTU Per Hour
040298, 040298A, 040301, 040315,
040320
29.1 Amps
240 Volts
Single Phase
77°F (25°C)
-20°F to 104°F (-28.8°C to 40°C)
11 - 14 in. W.C.
33c / 82,500b
56c / 140,000b
5 - 7 in. W.C.
80c / 80,000b
137c / 137,000b
7.5 - 9.3 OHM
0.20 - 0.26/0.20 - 0.26 OHM
2.06 - 2.50 OHM
200 LB-IN (23 Nm)
200 LB-IN (23 Nm)
200 LB-IN (23 Nm)
50 LB-IN (7 Nm)
80 LB-IN (9 Nm)
80 LB-IN (9 Nm)
220 LB-IN (25 Nm)
60Hz
4