Drain joint installation

Fit the seal into the drain elbow, then insert the drain joint into the base pan hole in the bottom of the
outdoor unit, rotate 90° to assemble them securely. Connect the drain joint with an extension drain hose
(not included). In this way condensed water, which is produced during heating mode of the air conditioner,
can be drained away. See fig. 16.
9.

ELECTRICAL WORK

Connect the air conditioner to a separate group. Ensure that this group has the correct fuse
See following table.
Power voltage supplied should be in the range of 95%~105% of rated voltage on rating table.
The power supply must have an earth leak switch installed.
Ensure the air conditioner is grounded well.
Connect the wires according the attached electrical connection diagram located on the panel of the
outdoor unit. See chapter 11
All wiring must comply with local and national electrical standards and codes and be installed by
qualified and skilled people.
Model
≤ 3,5 kW
> 3,5 kW
G
NOTE!
The supply voltage should be consistent with the rated voltage of the air conditioner.

10. CONNECTING THE ELECTRICAL CABLES.

a.
Connect the cable to the indoor unit
b.
Indoor/Outdoor connection cable should be H07RN-F type, 2,5 mm².
c.
To mount the cable to the interior unit: Remove the front panel and the cover plate of the terminal
strip on the right hand side of the interior unit. Figure 19.
Q_instal_S-JA2518 ('17) V2.indd 31
Drain joint
Seal
Base pan hole of
outdoor unit
Figure 16
Power supply
230V~50Hz
230V~50Hz
Seal
Drain pipe
Input Rated Current
(Switch/Fuse)
16A
16A slow
Power cord size
2,5 mm
2
2,5 mm
2
4
31
31
30-10-17 14:42