7 Troubleshooting

7.1 Troubleshooting
Engine does not turn when starter is actuated
Cause
Battery/UltraCaps low or
defective
Cable connections faulty
Starter: plant starter controller or
starter faulty
Engine wiring defective
Engine / generator control:
Assemblies or plug-in connections
loose
Engine governor: Plug-in
connections loose
Barring tool installed
Running gear blocked (engine
cannot be barred manually)
Engine transport locking device
installed
External transport locking device
installed
External cranking lock activated
Engine turns but does not fire
Cause
Engine too cold
High load, e.g. gearbox engaged
Poor rotation by starter: Battery/
UltraCaps low or defective
Engine wiring defective
Air in fuel system
Engine governor defective
78 | Troubleshooting | MS15041/03E 2018-08
Corrective action
u Charge or replace (→ manufacturer's documentation)
u Check cable connections for secure seating (→ manufacturer's
documentation)
1. Visual inspection procedure
2. Check whether cable connections are properly secured
3. Contact Service
u Check (→ Page 251)
u Perform visual inspection (→ manufacturer's documentation).
u Check plug-in connections (→ Page 256)
u Remove barring tool (→ Page 154)
u Contact Service
u Remove transport locking device (→ Page 20)
u Remove external transport locking device
u Deactivate external cranking lock
Corrective action
u Preheat (25 °C)
u Reduce load
u Charge or replace battery/UltraCaps (→ manufacturer's
documentation)
u Check (→ Page 251)
u Vent fuel system (→ Page 182)
u Contact Service