10-40kVA UPS INTALLATION & USER MANUAL SAFEPOWER S KEEP FOR FUTURE REFERENCE for the entire life of the appliance IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 1 di 50 + FR...
Page 2
EMC and safety standards, The UPS meets the world’s advanced level. Read this manual carefully before installation This manual provides technical support to the operator of the equipment. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 2 di 50 + FR...
Appendix 4 RS232 communication port definition ................46 Appendix 5 RS485 communication port definition ................48 Appendix 6 Dry contact port communication port definition ............49 Appendix 7 REPO instruction ........................50 IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 3 di 50 + FR...
Area with erosive gas, flammable gas, excessive dust, etc 8 Keep ventilations in good conditions otherwise the components inside the UPS will be over-heated which may affect the life of the UPS. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 4 di 50 + FR...
Intelligent Charging Method The series UPS adopts advanced three-stage charging method— stage: high current constant current charging to guarantee to charge back to 90%; IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 5 di 50 + FR...
UPS if any damage found. Please contact the dealer right away. 3. Check the accessories according to the packing list and contact the dealer in case of missing parts. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 6 di 50 + FR...
An unused battery must be recharged every 6months Temporarily connecting the UPS to a suitable AC supply mains and activating it for the time required for recharging the batteries. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 10 di 50 + FR...
Check to see if these supplies are electrically isolated. And post and necessary warning signs to prevent any inadvertent operation. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 11 di 50 + FR...
Page 12
For Grounding connection, follow the shortest route possible. WARNING! Failure to follow adequate earthing procedures may result in electromagnetic interference or in hazards involving electric shock and fire IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 12 di 50 + FR...
Choose appropriate power cable. (Refer to the table above) and pay attention to the diameter of the connection terminal of the cable that should be greater than or equal to that of the connection poles; IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 13 di 50 + FR...
The user can choose the capacity and the numbers of the batteries according to their desire. External battery connections for long-run units. 40kVA: IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 14 di 50 + FR...
Page 15
(+) to (+) / (-) to (-) but disconnect one or more battery cell links in each tier. Do not reconnect these links and do not close the battery circuit breaker unless authorized by the commissioning engineer. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 15 di 50 + FR...
3) The length and specification of power cables including the bypass input cables and the UPS output cables should be the same. This facilitates load sharing when operating in bypass mode. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 16 di 50 + FR...
UPS , baud rate choose 9600, protocol choose “HIP”, then save this setting. On the main page of Muser4000, click the button of “Append”, then goes to a window of “Append equipment”. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 17 di 50 + FR...
Page 18
CAUTION! When the UPS worked on inverter. If you want to use PC to set the output voltage and frequency. Must shut down the inverter first IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 18 di 50 + FR...
A manual bypass switch is available to ensure continuity of supply to the critical load when the UPS is out of order or in repair and this manual bypass switch bears for equivalent rated load. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22...
If the Rectifier input is within voltage range, the rectifier will start up in 30 seconds then the inverter will start up after then. Switch ON UPS OUTPUT breaker. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 20 di 50 + FR...
Page 21
Open BATTERY breaker; Switch OFF the MAINS breaker, Switch OFF OUTPUT breaker; At this time the bypass source will supply to the load through the MAINTENANCE breaker . IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 21 di 50 + FR...
Page 22
Turn on the Output switch. Switch ON the power switch (power will feed to auxiliary power board). Trigger the cold start button as the position 5 of the below drawing. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 22 di 50 + FR...
Page 23
Press OFF to shut down the UPS, waiting about 30s. Open the BATTERY breaker for long run UPS. Open the battery power switch for standard UPS. Open the OUTPUT breaker. The UPS shuts down. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 23 di 50 + FR...
Page 24
Connect the UPS with computer. Power on the UPS. Open Muser4000 software, after connecting with the UPS successfully, click “System”->“User Set” Click “Set” at “User Set” window; IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 24 di 50 + FR...
Page 25
At the window of “Data Set”, click “Ups ID”, write a value for the parallel UPS ID at the right side, such as “1”, then click “Set” as shown in below picture. If the UPS sounds a “beep”, that means the setting is correct. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 25 di 50 + FR...
(1)LED indicator (2)LCD display (3)Scroll button: enter to next item (4)Off button (5)On button Introduction CAUTION! The display provides more functions than those described in this manual. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 26 di 50 + FR...
Page 27
Operational Status and mode (When the UPS at single mode, it shows “NOR” or “ECO”, but If the UPS at parallel mode, it shows “PAL” instead.) 2) Press “scroll” button, the UPS goes to next page as shown below. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 27 di 50 + FR...
Page 28
2. Phase A (L1) Input/Frequency 3. Phase B (L2) Input/Frequency 4. Phase C (L3) Input/Frequency 5. Bat + (Positive) 6. Bat - (Negative) 7. Backup time IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 28 di 50 + FR...
Page 29
9. Phase B (L2) Output Voltage/Frequency 10. Phase C (L3) Output Voltage/Frequency 11. Phase A (L1) Load Capacity 12. Phase B (L2) Load Capacity 13. Phase C (L3) Load Capacity IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 29 di 50 + FR...
Page 30
3) Pressing “scroll” button, you may circulate all messages from the first one to the last one then returns back to the first one and vice versa. 4) All alarm codes are present when abnormal behavior(s) occur(s). IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 30 di 50 + FR...
Press “OFF” to exit the output voltage setting, and goes to mode setting. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 31 di 50 + FR...
Page 32
The battery capacity line flashes as in above picture. Use button “P” to choose the different battery capacity. Battery capacity range is 1-999Ah. (Note: long-press of “P” can IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 32 di 50 + FR...
Page 33
Press “OFF” to exit the bypass voltage upper limit setting and goes to battery quantity setting. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 33 di 50 + FR...
Page 34
Press button “ON” exits mute setting and save mute setting state and change to battery self-test settings. Press button “OFF” exits mute setting and change to bypass voltage lower limit setting. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 34 di 50 + FR...
Page 35
Press “OFF” to exit the battery sensor setting and transfer to battery periodical battery self-test setting. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 35 di 50 + FR...
Page 36
ID setting value and goes to parallel quantity setting. press “OFF” to exit the parallel ID setting and goes to device address setting. CAUTION! Parallel cable cannot be connected when setting the parallel parameters. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 36 di 50 + FR...
Page 37
“ON” to exit the mode setting and save the mode setting value and then UPS LCD panel setting is accomplished. Press “OFF” to go to parallel quantity setting. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 37 di 50 + FR...
9) Connected the Load, and check whether the output current are balance. Switch on and off the utility breaker to test all the UPS converters system from Utility to battery and restored function are working find IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 38 di 50 + FR...
Input neutral loss Twice per second Fault LED lit Battery reverse Twice per second Fault LED lit Cable connection error Twice per second Fault LED lit IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 39 di 50 + FR...
(such as UJPS failure, mains interruption, UPS bypass and ect.). It is installed in the intelligent slot of the UPS. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 40 di 50 + FR...
Power Factor Voltage Regulation ±1% Utility Output ±1%, ±2%, ±4%, ±5%, ±10% of the rated frequency(optional) Mode Frequency Battery (50/60±0.2%)Hz Mode Crest Factor ≤2% with linear load IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 41 di 50 + FR...
Page 42
0 95% non condensing Altitude < 1500m.When>1500m,lower the rated power for use Dimensions(D×W×H ) 828x250x868 Other Weight (Kg) 115/57 170/63 171/64 Safety Conformance CE,EN/IEC 62040-2,EN/IEC 62040-1-1 IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 42 di 50 + FR...
Page 43
Breaker 63A Breaker 80A Mode Short Circuit 164A Peak Line Mode: Switch to Bypass; Backup Mode: Shut down UPS Overheat immediately Battery Low Alarm and Switch off IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 43 di 50 + FR...
If the UPS operates at battery mode, Utility voltage exceeds please pay attention to the Utility LED is flashing UPS input range. remaining backup time needed for your system. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 44 di 50 + FR...
Page 45
Buzzer beeps continuously and LCD Consult with your local agent for UPS is out of order indicates 1,3,5,9,15, etc repair fault codes IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 45 di 50 + FR...
USB, RS232 and RS485 interface cannot be used at the same time, you can only use one of them at one time. Appendix 4 RS232 communication port definition IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 46 di 50 + FR...
Page 47
Parity check ---------none CAUTION! USB, RS232 and RS485 interface cannot be used at the same time, you can only use one of them at one time. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 47 di 50 + FR...
USB, RS232 and RS485 interface cannot be used at the same time, you can only use one of them at one time. RS485 port pin7 is 12Vdc! IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 48 di 50 + FR...
Pin1 UPS Battery Low Pin2 AC Power Failure Pin3 Turn off UPS Pin4 Common GND Function description: Monitor UPS status; Monitor UPS battery status; Shutdown UPS. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 49 di 50 + FR...
REPO connector. The remote switch can be connected to several UPS in a parallel architecture allowing the user to stops all units at once. IV405E Rev.000 SIEL S.p.A. Data di emissione: 2018-06-22 Pag. 50 di 50 + FR...