POSITION 2
DIALER
FCA2015-U1
Figure 2 – Power Connection to Dialer
INSTALLATION
1. Remove all system power before installation, first battery then AC. To power up, connect the
AC first, then the battery.
2. Mount the dialer bracket in either row 1 or row 2 of the inner door, using the two locknuts
provided.
3. Mount the dialer Model FCA2015-U1, P/N S54400-A63-A1, on the bracket using the four
screws provided with the Dialer.
4. Remove the plastic rear cover of the PMI by removing only the four screws.
5. Connect the cable harness provided to the PMI connector header and to the Dialer.
6. Plug the 2-pos connector provided into the dialer as shown in Figure 2. Use two 12-22 AWG
wires to connect it to the power supply. Connect the black wire from connector TB3 "Position
2" to the connector on the dialer X102 "Position 2". See Figure 2.
7. Reinstall the PMI rear cover that was removed in Step 4.
8. Refer to the FCA2015-U1 DACT Installation Instructions, Document ID A6V10334254, for more
information, including telephone connection wiring.
9. Apply power to the system.
10. Configure using Zeus programming tool.
NOTE: See the Zeus Quick-Start Manual, P/N 315-033875, for details on programming.
11. Check for proper operation.