Carrier AquaEdge 19DV series Start-Up, Operation And Maintenance Instructions Manual page 28

Two-stage back-to-back centrifugal liquid chillers with pic5 controls and hfo r-1233zd(e) 50/60 hz
Table of Contents

Advertisement

DESCRIPTION
Factory Password
Chiller Type
19XR6/7=0,
19XR2~E/D/V=1,
19DV=2
Unit Type
Cool Only=0, Heat Mach=1
Comp (Single=0, Dual=1)
Chilled Medium Type
Water/Brine
Cond Shell Side MAWP
185PSI=0, 300PSI=1
19DV Comp Design Press
44PSI=0, 72PSI=1
Country Code
Free Cooling Option
VFD Option
No=0,FS VFD=1,Carrier=2,
Rockwell LF2=3, Eaton=4,
Rockwell STD=5
IOB3 Option (19XR2~E/D/V)
IOB4 Option
Guide Vane1 Type,
Digital=0, Analog=1
VFD Feedback Voltage Sel,
0-5V=0, 0-10V=1
Marine Option
Power Request Option
Cont. Power Request
Purge System Option
Liquid Bypass Option
Heat Reclaim Option
No=0, Full=1, Partial=2
Main Menu
DESCRIPTION
VFD Gain
VFD Max Speed Per
VFD Min Speed Per
VFD Start Speed Per
VFD Current Limit
VFD Load Current 20mA
Comp Frequency 100%
VFD Load Current Input
Main Menu
DESCRIPTION
Motor Pole Pair
IGV2 Travel Limit
IGV2 minimum Degree
IGV2 Fully Open Degree
IGV2 Actuator Max Deg.
IGV2 Deg@IGV1 20 Deg
IGV2 Deg@IGV1 30 Deg
IGV2 Deg@IGV1 50 Deg
VFD Rate Speed Hz
Purge Regen Lasting Time
Daily PG Pumpout Limit
Table 9 — Factory Parameters
RANGE
0 to 65535
0 to 2
0 to 1
0 to 1
Water/Brine
0 to 1
0 to 1
0 to 999
No/Yes
0 to 5
0 to 1
No/Yes
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
Dsable/Enable
Dsable/Enable
0 to 2
Table 10 — General VFD Config
Configuration Menu
RANGE
0.10 to 1.50
90.0 to 110.0
45.0 to 89.0
65.0 to 100.0
0.0 to 99999.0
10.0 to 5000.0
45.0 to 62.0
Enable/Dsable
Table 11 — 19DV Configuration
Configuration Menu
RANGE
1, 2
30 to 100%
0 to 20
10 to 100
90 to 120
10 to 30
10 to 50
10 to 80
10 to 200
0 to 65535
20 to 200
UNITS
General VFD Config [CFGGEVFD]
UNITS
-
%
%
%
AMPS
AMPS
Hz
-
19DV Configuration [Table = CFG_19DV]
UNITS
-
%
Degree
Degree
Degree
Degree
Degree
Degree
Hz
minutes
minutes
28
DEFAULT
VALUE
4444
0
0
Per selection
1
Water
Per selection
1
0
86
No
Per selection
0
0
No
Yes
0
0
0
0
0
Dsable
Enable
Dsable
Per selection
0
DEFAULT
VALUE
0.75
0.75
100
100
70
100
100
250
Nameplate
200
50
Nameplate
Enable
Dsable
DEFAULT
VALUE
1
96
93.6
2
90
94
28.1
28.1
37.2
37.2
71.6
71.6
80.5
80.5
120
120
50
n/a
2
1
n/a
1
01
2
n/a
1
n/a
n/a
n/a
n/a
n/a
60
n/a
1
2
88
94
50

Advertisement

Table of Contents
loading