MACHINE SAFETIES
EVAPORATOR PUMP
CONDENSER
WATER PUMP
WATER FLOW, CHILLED WATER
TEMP, GUIDE VANES, REF PUMP,
TOWER FAN CONTROL
REF PUMP
COMPRESSOR,
COMPRESSOR ONTIME,
SERVICE ONTIME
15-MINUTE
START-TO-START
2-MINUTE
STOP-TO-START
PURGE DRAIN
3-WAY
ACTUATED
VALVE
STARTS IN 12 HOURS 8 (not counting recycle restarts or auto restarts after power failure)
COND PRESSURE COND PRESS OVERRIDE – 20 psi
#RECYCLE RESTARTS LAST 4 HOURS > 5
COMP BEARING TEMP >= COMP BEARING ALERT– 10°F (5.6°C)
COMP MOTOR WINDING TEMP COMP MOTOR WINDING– 10°F (5.6°C)
COMP DISCHARGE TEMPERATURE COMP DISCHARGE ALERT– 10°F (5.6°C)
EVAP_SAT <Evap trip point** + EVAP OVERRIDE DELTA T
EVAP REFRIG LIQUID TEMP <Evap trip point** + EVAP OVERRIDE DELTA T
AVERAGE LINE VOLTAGE UNDERVOLTAGE THRESHOLD
AVERAGE LINE VOLTAGE OVERVOLTAGE THRESHOLD
CHECK FOR GUIDE VANE 1 CALIBRATION
CHECK FOR GUIDE VANE 2 CALIBRATION
* If Prestart Check Condition is True, then resulting State is as indi-
cated in the State Number column.
† See the Controls Operation and Troubleshooting guide for alarm
and alert codes.
Fig. 12 — Control Timing Sequence for Normal Start-Up
STRAINER
SIGHT GLASS
STRAINER
2-WAY
ACTUATED VALVE
PUMP
Fig. 13 — Lube Assembly Schematic
Table 2 — Prestart Checks
PRESTART CHECK CONDITION*
††
††
START INITIATED: prestart checks are made; cooler pump
A
started.*
B
Condenser water pump started (5 seconds after A).
Water flows verified (30 seconds to 5 minutes maximum
after B). Chilled water temperatures checked against control
C
point. Guide vanes checked for closure. Refrigerant pump
started; tower fan control enabled.
Ref pressure verified (15 seconds minimum, 300 seconds
D
maximum after C).
Compressor motor starts; compressor on-time and service
on-time start, 15-minute inhibit timer starts (10 seconds after
E
D), total compressor starts advances by one, and the num-
ber of starts over a 12-hour period advances by one.
SHUTDOWN INITIATED; Compressor motor stops; com-
F
pressor on-time and service on-time stop, and 2-minute
inhibit timer starts.
Refrigerant pump and cooler pumps de-energized (120 sec-
onds after F).Condenser pump and tower fan control may
G
continue to operate if condenser pressure is high. Cooler
pump may continue if in RECYCLE mode.
Restart permitted (both inhibit timers expired: minimum of 15
O/A
minutes after E; minimum of 2 minutes after F).
*
Auto Restart After Power Failure Timing sequence will be faster.
COOLER
REFRIGERANT FILTER
** Evap trip point = 33°F (0.6°C) (water) or EVAP REFRIG TRIP-
POINT (brine).
††Condition ignored for Eaton/Rockwell VFDs.
14
HS FLOAT CHAMBER
BEARING
SUPPLY
BEARING FILTER
PUMPOUT
DRAIN
STATE NUMBER
Alert – 100
Alert – 102
Alert – 103
Alarm – 230
Alarm – 231
Alarm – 232
Alarm – 233
Alarm – 233
Alarm – 234
Alarm – 235
Alarm – 236
Alarm – 238
†