After the compres-
Check the Running System —
sor starts, the operator should monitor the display and observe
the parameters for normal operating conditions:
1. The normal bearing temperature should be about 95°F
(35°C). Alert will initiate at 104°F (40°C) and Alarm
will be initiated at 122°F (50°C).
2. The First Stage and Second Stage Bearing Tempera-
tures can be accessed from the Temperatures menu. If
the bearing temperature is high or in Alarm/Alert state
with the refrigerant pump running, stop the chiller and
determine the cause of the high temperature. Do not
restart the chiller until corrected.
3. The liquid level sensor on the condenser float chamber
should indicate Closed in the INPUT menu.
4. The bearing pressure drop should exceed 13 psid
(90 kPa) when the compressor is ON, as seen on the
HMI Transmission Status screen. If not an alert will be
generated. Typically the reading will be slightly lower at
initial start-up. There will be an alarm if compressor is
ON and the bearing pressure drop is less than 10 psid for
10 seconds.
5. The moisture indicator sight glass on the refrigerant mo-
tor cooling line should indicate single phase refrigerant
flow and a dry condition.
6. The condenser pressure and temperature varies with the
chiller design conditions. Typically the pressure will
range from -1.5 to 17.5 psig (-10.3 to 120.6 kPa). with a
corresponding temperature range of 60 to 105°F (15 to
41°C). The condenser entering water temperature should
be controlled below the specified design entering water
temperature to save on compressor kilowatt requirements.
7. Cooler pressure and temperature also will vary with the
design conditions. Typical pressure range will be between
-7.7 to -5.0 psig (-50.8 kPa to -35 kPa), with temperature
ranging between 34 and 45°F (1.1 and 7.2°C).
8. The compressor may operate at full capacity for a short
time after the pulldown ramping has ended, even though
the building load is small. The active electrical demand
setting can be overridden to limit the compressor kW, or
the pulldown rate can be decreased to avoid a high
demand charge for the short period of high demand oper-
ation. Pulldown rate can be based on load rate or tempera-
ture rate and is viewed at MAINTENANCE MENU
CAPACITY CONTROLS RAMP_DEM (Ramping
Demand Limit Value). Configuration done in General
Config and rate done in Service Parameters.
9. High and low float chambers each provide two sight
glasses for looking into the float chamber to confirm
proper float operation.
The occupancy schedule starts
To Stop the Chiller —
and stops the chiller automatically once the time schedule is
configured.
The unit can be stopped manually using the HMI by press-
ing the green Start/Stop icon
. The Unit Start/Stop screen is
displayed. Press Confirm Stop. The compressor will then fol-
low the normal shutdown sequence as described in the Start-
Up/Shutdown/Recycle Sequence section on page 12. The
chiller is now in the OFF control mode.
IMPORTANT: Do not attempt to stop the chiller by opening
an isolating knife switch. High intensity arcing may occur.
If the chiller is stopped by an alarm condition, do not restart
the chiller until the problem is diagnosed and corrected.
No special preparations
After Limited Shutdown —
should be necessary. Follow the regular preliminary checks and
starting procedures.