Installation and Wiring

Safety Considerations

Publication 1761-UM004B-EN-P - June 2006
This equipment is suitable for use in Class I, Division 2, Groups A, B,
C, D, or nonhazardous locations only.
Explosion Hazard —
ATTENTION
Substitution of components may impair suitability for Class I,
Division 2.
Do not replace components or disconnect equipment unless
power is switched off and the area is known to be
nonhazardous.
Do not connect or disconnect connectors or operate switches
while circuit is live unless the area is known to be
nonhazardous.
This product must be installed in an enclosure. All cables
connected to the product must remain in the enclosure or be
protected by conduit or other means.
AIC+ interface converter must be operated from an external
power source.
All wiring must comply with N.E.C. articles 501, 502, 503,
and/or C.E.C. Section 18-1J2, as appropriate.
Use only the following communication cables and replacement
connectors in Class I, Division 2, hazardous locations.
Communication Cables for Class 1, Div Environments
Environment Classification
Class I, Division 2 Hazardous Environment
Communication Cables
1761-CBL-PM02 (Series C or later)
1761-CBL-HM02 (Series C or later)
1761-CBL-AM00 (Series C or later)
1761-CBL-AP00 (Series C or later)
2707-NC8 (Series B)
2707-NC9 (Series B)
2707-NC10 (Series B)
2707-NC11 (Series B)
1746-RT30 AIC+ Connector