Technibel iSeries Technical Data & Service Manual page 18

Table of Contents

Advertisement

Crankcase heater
Crankcase heater around the compressor is used to prevent refrigerant migration and mixing with
crankcase oil when the unit is off, and to prevent condensation of refrigerant in the crankcase of the
compressor. The crankcase heater keeps refrigerant at a temperature higher than the coldest part of the
system.
Crankcase heater is activated if the following conditions are met:
Compressor is stopped
-
OAT il lower than 5°C
-
Difference between CDT and OAT is lower than 18,5°C
-
When crankcase is active, it will be deactivated if one of the following condition is met:
Compressor starts
-
OAT increases above 5°C
-
Difference between CDT and OAT is higher than 21,5°C
-
Drip tray heater (built-in) and condensation water heater (accessory)
The drip tray heater and the condensation water heater prevent condensation freezing on the drip tray
and the condensation water pipe.
The heaters are activated if the system is in heating mode and one or more of the following conditions
are met:
OAT is lower than 0°C
-
Defrost is active
-
Less than 5 minutes have passed since last defrost
-
When heaters are active, they will be deactivated if all of the following conditions are met:
OAT is higher than 2°C
-
Defrost is not active and more than 5 minutes have passed since last defrost
-