Deploying New Hardware As Replacement - Siemens SIMATIC PCS 7 Operation And Maintenance

Process control system pcs 7 compendium part d
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Replacing hardware

4.2 Deploying new hardware as replacement

4.2
Deploying new hardware as replacement
If no successor module has yet been listed in the manual titled "PCS 7 – Released Modules"
(https://support.industry.siemens.com/cs/ww/en/view/109748745) and no related information
appears in the PCS 7 Readme (online)
(https://support.industry.siemens.com/cs/ww/en/view/109744312), the successor module can
be used in spare part-compatible operation. The replacement scenario is described in the
corresponding delivery release.
Note
The following always applies when replacing hardware: The old hardware component has
been configured and the new hardware component which is compatible as a replacement is
then deployed.
When a new hardware component is deployed as a replacement, it will not be possible to
use its advanced functions.
Example: Using IM 153-2 BAxx in PCS 7 V6.1 SPx
An IM 153-2 interface module (used for ET 200M, DP/PA link, and Y link) is presented here
as an example.
The "Readme.txt" file for PCS 7 V6.1 SP3 contains the following description with regard to
the IM 153-2BAxx:
"The following updated AS hardware components can be used with PCS 7 V6.1 SP3 in
addition to the AS hardware components listed in the document titled "PCS 7 - Released
Modules" (the listed hardware support packages are integrated).
Product
ET 200M IM 153-2BAx1 *
ET 200M IM 153-2BAx2 *
* = Only in spare part-compatible operation (use of the corresponding hardware is possible
only by means of the configuration of the predecessor module released for PCS 7 or the
previous and released firmware version)."
This means that the following, new ET 200M functions cannot be used with PCS 7 V6.1 SP2
and SP3 yet but only with PCS 7 V7.0 SP1:
● Configuring 12 modules in a single ET 200M
● High-precision time stamping with 1 ms
● Use of HART primary and secondary variables for 8-channel ET 200M HART module
40
Modules
6GK7 153-2BA01-0XB0;
6GK7 153-2BA81-0XB0
6GK7 153-2BA02-0XB0,
6GK7 153-2BA82-0XB0
Compendium Part D - Operation and Maintenance (V9.0)
Operating Manual, 02/2018, A5E43228948-AA