Siemens SIMATIC PCS 7 Operation And Maintenance page 59

Process control system pcs 7 compendium part d
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

4. Open the process device plant view in SIMATIC Manager. Sort the devices to list those
with no description file. You can display the "Devices" column in SIMATIC Manager under
"Options > Settings > Columns > Process Device Plant View".
If no device description has been assigned to a configured device, its symbol will be
displayed in gray. The device description (EDD) file is not installed in this example. You
receive the following message when you double-click on this device:
You can use the Device Integration Manager to display the available and missing device
descriptions in your projects.
Note
A PCS 7 project can contain information about device descriptions which are no longer
used in the project. In this case, you need to carry out a "Save with reorganization" for the
project.
Compendium Part D - Operation and Maintenance (V9.0)
Operating Manual, 02/2018, A5E43228948-AA
Service and maintenance of SIMATIC PDM
6.4 Updating SIMATIC PDM
59