COOPER POWER Fusing Equipment Effective November 2016 SERIES Supersedes MN132016EN September 2005 (S240-71-1) ELF-LR™ Current-Limiting Fuse Installation Instructions...
CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to...
FOR LIFE FOR LIFE Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power™ series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service.
. Eaton’s Cooper Power series ELF-LR™ Current-Limiting Fuse is a full-range current-limiting fuse that is suitable for use in areas where a high-fire hazard exists. ELF-LR liquid fuses are noiseless and expel no hot gases or burning particles while performing fault current interruptions.
ELF-LR™ Current-Limiting Fuse Removal Open cutout locking clips. Using fuse puller, remove lower end of fuse from cutout first, then upper end (see Figure 3). Figure 2 . Installing fuse in cutout . Figure 3 . Proper removal of fuse in cutout . CAUTION CAUTION If a fault is present when installing an ELF-LR fuse, the...
ELF-LR™ Current-Limiting Fuse Testing A continuity test in the field can determine if the fuse element is open. This can be done using an ohmmeter or self-powered continuity tester. To confirm the integrity of the current-limiting section, additional shop testing using a micro-ohmmeter to verify the nominal resistance is recommended (See Table 1).