the rated current of the fuse and the rated current I
and it is within this margin that selectivity is implemented.
Previous selectivity assessments indicated that an upstream molded case circuit breaker
with a rated current I
installed downstream.
Thanks to the ELISA function of the ETU340 of the 3VA2 molded case circuit breaker, for
example, total selectivity is afforded between an upstream 3VA2 molded case circuit breaker
with a rated current I
advantageous feature allows users to choose cheaper circuit breakers and configure
additional grading levels more easily in low-voltage networks.
Selectivity for 3VA molded case circuit breakers
Configuration Manual, 08/2016, A5E03603181010-01
Selectivity implemented by combinations of protective devices
of at least 250 A would be required if a 100 A LV HRC fuse were
rated
of just 160 A and a downstream 100 A LV HRC fuse. This
rated
4.4 Fuse and downstream fuse
of the molded case circuit breaker