Binary Output Status Points - HindlePower AT Series Operating Instructions Manual

Microprocessor-controlled float battery charger, communications module, dnp3 level 2 / modbus protocols
Hide thumbs Also See for AT Series:
Table of Contents

Advertisement

DNP V3.00

5.4.2 Binary Output Status Points

The following table lists both the Binary Output Status Points (Object 10).
Binary Output Status Points
Object Number:
Request Function Codes supported:
Default Variation reported
when variation 0 requested:
Control Relay Output Blocks
Object Number:
Request Function Codes supported:
Point
Name/Description
Index
0
Equalize Mode
1
Manual Timer Method
2
Manual Equalize Method
3
Auto-Equalize Timer Method
4
HVDC Shutdown Enable
5
Battery Type
Note: Only one equalize method can be on at a time. The equalize method cannot be turned
off. By turning on one of the equalize methods (point index 1, 2, or 3) the charger will
automatically turn off the other two equalize methods.
24
10
1 (read)
2 (Binary Output Status)
12
3 (select), 4 (operate)
5 (direct operate), 6 (direct operate, noack)
Methods
Latch On, Latch Off
Latch On
Latch On
Latch On
Latch On, Latch Off
Latch On, Latch Off
(0 = float; 1 = equalize)
(1 = enabled)
(1 = enabled)
(1 = enabled)
(1 = enabled)
(0 = lead; 1 = NiCD)