4.2 Setup Program

The setup program may only be used with an RS-232 serial connection. Use a terminal mode
program such as HyperTerminal with the baud rate set to 9600 bps, 8 data bits, no parity, 2
stop bits, and no hardware handshaking. Remove power to the charger by turning both AC
and DC circuit breakers off. To enable the setup program, set switch S1-1 to ON. To use the
user values for configuration parameters, set switch S1-2 to ON. Restore power to charger
by turning on the DC breaker first then the AC breaker. The following screen will appear:
-- EN5004 Setup --
1
2
3
4
5
6
7
8
To change a value, please select its item number:
To select an item to view and modify, enter the item number by typing the number and press
ENTER. The sample below shows item 1 DNP Device Address is selected. The current
value is set to 1. Entering a new value and pressing ENTER will accept the new value if it is
within the acceptable range. "Value written to memory" will be displayed if
accepted or "VALUE ENTERED IS OUT OF RANGE!" if not accepted. Pressing the
ESC key will cancel modifying the parameter and return to main menu.
To change a value, please select its item number: 1
DNP Device Address: 1 (Range 1 to 65,519),
Enter new value (ESC to cancel): 2
Value written to memory
If S1-2 is set to OFF for using factory default values, the parameters can be viewed. The
parameters can be modified but if S1-2 is still set to factory default values when power is
cycled, then all values will be changed back to factory defaults. Setting S1-2 ON will allow
USER values to be used. If S1-2 is OFF the screen will look like this:
-- EN5004 Setup --
USING DEFAULT VALUES (SWITCH S1-2 IS OFF)
CHANGED VALUES WILL NOT BE STORED
1
2
3
4
5
6
7
8
To change a value, please select its item number:
DNP Device Address
DNP Unsol Destination Address
DNP Unsol Messaging Enabled
DNP Unsol Timeout
DNP Unsol Retries Amount
DNP Unsol Indefinite Retries
Comm Parity
Comm Stop Bits
DNP Device Address
DNP Unsol Destination Address
DNP Unsol Messaging Enabled
DNP Unsol Timeout
DNP Unsol Retries Amount
DNP Unsol Indefinite Retries
Comm Parity
Comm Stop Bits
CONFIGURATION
15