CONFIGURATION

4 Configuration
All user configurable items are controlled by two groups of switches and a setup program to
modify additional configuration parameters. After changes have been made, the charger
must have both the AC and DC circuit breakers turned OFF then back ON again for any
changes to take affect.
S1 is used to configure the communications interface. S2 is used to set the device address for
Modbus. Setting S1-1 to enable the Setup Program, allows modification to additional
configuration parameters.

4.1 DIP Switch Settings

S1 Configuration
Position
DIP S1-1
DIP S1-2
DIP S1-3
DIP S1-4
DIP S1-5
DIP S1-6
DIP S1-7
DIP S1-8
*Note: See Configuration Parameters Below
S2 Modbus Network Address Selection
Switch Position
DIP S2-1
DIP S2-2
DIP S2-3
DIP S2-4
DIP S2-5
DIP S2-6
DIP S2-7
DIP S2-8
Modbus Slave Address Table
Slave
Address
1
1
0
2
0
3
0
4
0
5
0
6
0
255
1
14
Description
Setup Program
Configuration
Parameters*
Protocol
Modbus Protocol
Serial Port
RS-232 Handshaking
Baud Rate
Not Used
Address bit
Net addr b7
Net addr b6
Net addr b5
Net addr b4
Net addr b3
Net addr b2
Net addr b1
Net addr b0
DIP S2
2
3
4
5
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
"ON" position
"OFF" position
Enabled
Disabled
User Values
Factory Default
Values
DNP
Modbus
ASCII
RTU
RS-485
RS-232
Enabled
Disabled
19200 bps
9600 bps
6
7
8
0
0
1
0
1
0
0
1
1
1
0
0
1
0
1
1
1
0
1
1
1