Standard Connection Diagram

MCCB
Contactor
R
S
T
Note:Function description in brackets is
factory default
(Forward)
(Reverse)
(FWD JOG)
(REV JOG)
(Free STOP)
RS485 Differential
Communication
Shielded cable (the end close to
VFD grounding)
Analog Voltage/Current quantity input
Analog Voltage/Current quantity input
Note:
1.MAX Output of +10V port :50mA
2.Inner resistance of AI1/AI2 Port
Note: 1.When installing DC reactor, make sure to dismantle the short connector between terminal P1 and (+).
2. NPN or PNP transistor signal can be selected as input of multi-function input terminal (X1~X5/PUL) . Inverter built-in power supply
(+24V terminal) or external power supply (PLC terminal) can be chosen as bias voltage. Factory setting '+24V' short connect with
'PLC', which locates between RJ45 and terminals.
3. Analog monitor output is the special output for meters such as frequency meter, current meter and voltage meter. It can't be used for
control operations such as feedback control.
4. As there are multi pulse styles, please refer to the line connect mode description details.

Auxiliary Terminal Output Capacity

Terminal
Function Definition
+10V
10V auxiliary power supply output, constitutes loop with GND.
A0
Analog monitor output, constitutes loop with GND.
24V auxiliary power supply output, constitutes loop with COM.
+24V
Collector open circuit output; can set the action-object by
Y
program.
TA/TB/TC
Passive connector output; can set the action-object by program. 3A/240VAC
External Brake Unit
R
Input Rector
+
(-)
( )
R
S
T
Note2
+24V
PLC
COM
X1
X2
X3
X4
X5
PUL
COM
A+
120Ω
B-
+10V
AI1
AI2
GND
External DC Rector
External
Brake
Resistor
Short
Note1
Piece
+
+
( )
( )
PB
P1
U
V
W
VFD
E
TA
TB
TC
+24V
Y
COM
Note:
1.MAX Output of +24V Port:DC24V/100mA
A0
GND
Note:When output type of AO port as
Legend: 1.Symbol
Max Output
50mA
Max output 2mA as frequency, voltage signal
100mA
DC24V/50mA
6
Output Rector
U
V
W
Shielded cable or armoured cable
(the end close to VFD grounding)
(The grounding resistance
is less than 10 ohms)
AC220V
MAX Output Of Contact:
3A/240VAC
5A/30VDC
Coil
AC0V
Shielded cable
Coil
(the end close
to VFD grounding)
2.Max Output of Y Port :DC24V/50mA
10
_
mA
-
+
Shielded cable (the
end close to VFD
grounding)
frequency and Voltage,
Maximum Output:2mA
represent main circuit terminals;
represent control circuit terminals.