Motor Parameters - Veichi AC300 series Manual

Hide thumbs Also See for AC300 series:
Table of Contents

Advertisement

F04.26
Alarm selection 1
F04.27
Reserved
F04.28
Fan control
F04.29
Energy braking enable
Energy braking operation
F04.30
voltage
F04.31
Energy braking utilization
F04.32
PWM carrier frequency
F04.33
PWM control mode

Motor Parameters

NO.
Function description
F05.00
Motor mode
F05.01
Number of motor poles
F05.02
Motor rated power
F05.03
Motor rated frequency
F05.04
Motor rated speed
F05.05
Motor rated voltage
F05.06
Motor rated current
Asynchronous motor no-load
F05.07
current
Asynchronous motor stator
F05.08
resistance
Asynchronous motor rotor
F05.09
resistance
Asynchronous motor stator
F05.10
leakage inductance
LED "0" digit: E.EEP fault (EEPROM storage
fault)
0: Alarm and free stop
1: Alarm and continue operation
0:After power on the fan runs
1: Stop associated with temperature, running is
rotary
2: Running associated with temperature, stop
while the fan stops
0:Off
115.0%~140.0%
0.0~100.0%
0.7~16.0kHz
LED "0" digit: carrier associated with
temperature
0: Temperature independent
1: Temperature dependent
LED "00" digit : carrier associated with output
frequency
0:not associated
1: associated
LED "000" digit: random PWM valid
0: Prohibited
1: Valid
LED "0000" digit: PWM modulation mode
0: Only use three-phase modulation
1: Two-phase and three-phase modulation
automatically switched
Range of settings and definition
0: Asynchronous motors (AM)
1: Permanent magnet synchronous motors (PM)
2~98
0.1~1000.0kW
0.01~max frequency
1~65000rpm
1~1500V
0.1~3000.0A
0.1~3000.0A
0.01~50.00%
0.01~50.00%
0.01~50.00%
19
100.0%
0000
1:On
125.0%
10.0%
Model set
1111
Factory
default
Model set
Model set
Model set
Model set
Model set
Model set
Model set
Model set
Model set
0x41A
0x41B
1
0x41C
0
0x41D
0x41E
0x41F
0x420
0x421
Feat
Address
ure
0
×
0x500
4
0x501
0x502
0x503
0x504
0x505
0x506
0x507
0x508
0x509
0x50A