6 APPENDICES
The following tables display electrical and physical specifications and also communication interfaces and agency approval.
Appendix A: Specifications
Table 6.1 Electrical and Physical Specifications
PARAMETER
Voltage
Power
Operating Temperature Range,
Ambient Storage Temperature Range,
Relative Humidity
Maximum Operating Altitude, ft. (m)
Dimensions, WxDxH, in. (mm)
Table 6.2 Communication Interfaces and Agency Approval
COMMUNICATION PORTS
Ethernet
I2C
EIA562 RS-232
1-Wire
USB
Safety Standards
EMC Standards
Agency Approvals
Vertiv | RPC2™ Communications Module Installer/User Guide |
LIMITS
7-12 V DC
6.5 W Maximum
41 to 140 (5 to +60) °F (°C)
-40 to 140 (-40 to +60) °F (°C)
0% to 95% (non-condensing)
6560 (2000)
4.0 x 0.84 x 1.78 (101.6 x 21.3 x 45.2)
DESCRIPTION
2 (one 10/100/1000Mbps Port; one 10/100Mbps Port)
1 (interface to the RPC BDM)
1 (interface to Avocent appliances)
1 (interface to Liebert 1-wire sensors)
1 (supports memory stick configuration)
(Vary by model and region)
IEC 60950-1:2005 (2nd Edition) + Amendment 1:2009
CSA C22.2 NO. 60950-1-07 (2nd Edition) + Amendment 1:2009
UL 60950-1 (2nd Edition) + Amendment 1:2009
IECEE CB Full Certification Scheme
(Vary by model and region)
FCC Class A, Part 15, Industrial
EN55022:2006+A1:2007, Class A, Industrial
EN55024:1998+A1:2001+A2:2003, Class A, Industrial
IEC61000-3-2:2006, IEC61000-3-3:1995+A1:2001+A1:2005
IEC61000-4-2/3/4/5/6/8/11
(Vary by model and region) UL, cUL, CE, BV, PSE, CB, RoHS, REACH, WEEE