SNMPv3 Access
From the side navigation bar of the System tab, click SNMP-V3 Access to configure the SNMPv3 community's settings. Up
to 20 devices can be configured with permission to access the RPC2 communications module, identified by IP address or
hostname, read/write privileges and a community string.
Table 3.8 SNMPv3 Access Description
PARAMETER
Entry
User Enable
User Name
Authentication Type
Authentication
Secret
Privacy Type
Privacy Secret
Access
Source
Clear
NOTE: A configuration with sources set to 0.0.0.0 with write access and no authentication grants access to any host
computer.
SNMPv1/v2 Traps
An administrator can configure up to 20 users to receive notifications from the RPC2 communications module, identified by
IP address or hostname, trap listen port and community string.
To configure SNMPv1/v2 traps:
1.
From the side navigation bar of the System tab, click Manage Protocol - SNMP - V1V2 Traps.
2. Enter the network name, port number and community string in the appropriate fields.
3. Check the box to enable the heartbeat feature.
4. Click the Save icon in the upper-left of the window.
5. To verify the configuration, click the Verify icon at the upper-left of the window.
Table 3.9 SNMPv1/v2 Trap Descriptions
PARAMETER
Entry
Network Name
Port
Community
Heartbeat
Clear
Vertiv | RPC2™ Communications Module Installer/User Guide |
DESCRIPTION
As many as 20 devices can be configured for access.
User Enable must be checked for each user to be configured for access. A maximum of 20 devices may be configured for
access.
The IP address of the network host to receive access to device information or traps.
Options are none, MD-5 or SHA.
Password between 8-64 characters for SNMPv3 request.
Options are no encryption or DES.
Password of 8-64 characters for SNMPv3 request.
No Access provides no access. ReadOnly provides only the ability to view data.
Either an IP address or the network name of the host. To enable multiple hosts, enter network names separated by a comma.
Click Clear to delete all values for this entry.
DESCRIPTION
Enter up to 20 targets to receive traps.
The IP address or network name of the target to receive traps.
The Trap Listen Port where traps will be sent. Use 162 if the host computer uses standard ports.
The community string used the by the IP host for this entry (case sensitive, up to 32 characters).
Check the box to enable a heartbeat check.
Click Clear to delete all values for this entry.
28

Advertisement

Table of Contents
loading

Table of Contents