When unlocked, the zone set point can be modified by using the UP and DOWN
buttons. Simply press one of these buttons to display the set point. When the
appropriate set point is displayed, wait a few seconds and the set point will be saved.
The remote room sensor with address 2 can also be used to temporarily override
occupancy from one to nine hours. To override occupancy, press the SLEEP button on
the left side of the Remote Room Sensor. The SLEEP button, symbolized as a
crescent moon on the left side of the sensor, is the fourth button from the top. An icon
showing a crescent moon and the number of hours the occupancy will be overridden
is displayed. To increase the hours, press the SLEEP button repeatedly until the
appropriate number of hours is displayed. To disable the temporary override, press the
SLEEP button until "0" (zero) hours is displayed. The temporary override will now end.
Additionally, any Remote Room Sensor connected to the CM3500 will also display
important information such as an alarm condition, the occupied mode and whether the
room sensor network connection has failed. An alarm condition is displayed as "ALr"
and will flash between the room temperature and "ALr." A bell icon will also blink on
the display. The occupancy of the unit will be displayed as a house icon to the left of
the room temperature. If the house icon is empty, the dehumidifier is in the
un-occupied mode. If a human figure is in the house, the dehumidifier is in the
occupied mode. If the network connection has failed, "oLn" is displayed to indicate
that the Remote Room Sensor is offline.
Internal setup of the remote room sensor is accomplished by pressing the DOWN
button and, while holding the DOWN button, pressing the UP button for 4 seconds.
When the display blinks "Par", keep pressing the UP button, release the DOWN button
and press the bottom button on the left hand side of the sensor for three seconds.
The display will now show the current device address as "Ad01". Select and modify
respectively with the bottom button on the left hand side of the sensor, the UP and
DOWN buttons. "Ad01" is the pAD address, settable from 1 – 32. "br01" is the baud
rate and needs to be set at 0. "En01" set to 0 disables the buzzer. "Pc01" is the offset
of the zone temperature from -9.9 to 9.9.