Electrical Installation - BIG ASS FANS Sweat Bee Installation Manuals

Table of Contents

Advertisement

Safety cable (customer-supplied) installation
ATTENTION: Do not connect any safety cable or chain to the fan housing on either end of the fan. Do not
connect any safety cable or chain to an area near the blades where it could become entangled.
With every installation in which the fan is mounted above the floor, a safety cable or chain should be securely
connected between the fan and the mounting structure to limit how far the fan could fall if the mounting hardware
becomes loose� This safety feature should be installed by the user to prevent property damage, severe personal
injury, death, and to comply with local codes. The cable or chain should not be any longer than needed to operate
the fan properly and it should be strong enough to support a minimum of two (2) times the total weight of the fan
assembly�

Electrical installation

CAUTION: All wiring connections, inspection, and maintenance of any motor must be performed by a
licensed electrician in accordance with the motor manufacturer's recommendations, all electrical codes,
and OSHA regulations. Failure to properly install, wire, or perform any maintenance to a motor can result
in motor failure, property damage, injury, or death.
WARNING: Do not operate this fan from an ungrounded receptacle or use any device on the power cord
that can defeat proper earth ground such as a plug adapter.
WARNING: Exercise caution and common sense when powering the fan. Do not connect the fan to a
damaged or hazardous power source. Do not attempt to resolve electrical malfunctions or failures on your
own. Contact Big Ass Fans if you have any questions regarding the electrical installation of this fan.
WARNING: The installation and usage of a Big Ass Fan must be in accordance with the requirements
specified in this installation manual and with any additional requirements set forth by the national electric
code (NEC) and all local codes. Code compliance is ultimately YOUR responsibility! Failure to comply with
these codes could result in personal injury or property damage.
18-Inch Sweat Bee®. The 18-inch Sweat Bee is pre-wired for 115 volt, single-phase, 60 Hz, and includes a 12-ft cord
with a switch and a 3-prong, grounded plug�
30-Inch Sweat Bee®. If the fan is a 30-inch Sweat Bee, the motor must be wired according to the schematic
located on the motor itself� A licensed electrician must supply required electrical components and complete the
wiring connections from the motor to an outside conduit box� Note: The cage guard must be removed to access
the motor.
Power requirements
Fan size
Motor size
18 in�
1/3 hp
30 in�
1 hp
Note: Assumes the use of an Inverse Time Circuit Breaker (I2t).
Supply circuit size
20 A @ 100–125 V, 1 Ф
15 A @ 200–220, 3 Ф
15 A @ 400–480 V, 3 Ф
877-BIG-FANS
© 2012 DELTA T CORP.
Full load current
6 A @ 100–125 V, 1 Ф, 60 Hz
3�7 A @ 200–220, 3 Ф
1�9 A @ 400–480 V, 3 Ф
ALL RIGHTS RESERVED
003489-01
Maximum ambient
operating temperature
104°F (40°C)
104°F (40°C)
REV. I