22
SLC 500™ Analog I/O Modules
Specifications
General Specifications for NI4, NIO4I, NIO4V, NO4I,
NO4V, FIO4I, FIO4V
Description
SLC Communication Format
Field Wiring to Backplane Isolation
Update Time
Recommended Cable
Maximum Wire Size
Terminal Block
Location
Calibration
Noise Immunity
Environmental Conditions
Operating Temperature
Storage Temperature
Relative Humidity
Agency Certification
(when product or packaging is marked)
(1) See the customer calibration program and procedure in the SLC 500 Fast Analog I/O Modules
User Manual, publication number 1746-6.9.
Publication 1746-IN008A-US-P
Specification
16-Bit Two's Complement Binary
500V dc
512 µs for all channels in parallel
Shielded Belden #8761
#14 AWG (maximum)
Removable
1746 chassis
Factory Calibrated
NEMA Standard ICS 2-230
to +60
°
°
0
C (+32
to +85
°
°
-40
C (-40
5 to 95% (non-condensing)
• CSA certified
• Hazardous Location Class I, Division 2
Groups A, B, C, D certified
• UL listed
• CE marked for all applicable directives
(1)
to +140
°
°
F)
to +185
°
°
F)