Wiring the Finger-Safe Terminal Block
ATTENTION
!
When wiring the terminal block, keep the finger-safe cover in place.
1. Route the wire under the terminal pressure plate. You can use the stripped
end of the wire or a spade lug. The terminals will accept a 6.35 mm
(0.25 in.) spade lug.
2. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.904 Nm (8
in-lbs).
3. After wiring is complete, remove the debris shield.
TIP
Be careful when stripping wires. Wire fragments that fall into a
module could cause damage when power is applied. Once
wiring is complete, ensure the module is free of all metal
fragments.
If you need to remove the finger-safe cover, insert a screw driver
into one of the square wiring holes and gently pry the cover off.
If you wire the terminal block with the finger-safe cover
removed, you will not be able to put it back on the terminal
block because the wires will be in the way.