Allen-Bradley MicroLogix 1200 Installation Instructions Manual page 13

Isolated relay output module
Hide thumbs Also See for MicroLogix 1200:
Table of Contents

Advertisement

Relay Contact Ratings
Maximum
Amps per
Volts (max.)
(ac:50/60 Hz)
(Resistive)
240V ac
120V ac
125V dc
24V dc
(1)
The continuous current per module must be limited so the module power does not exceed 1440VA.
(2)
6 A in ambient temperatures above 40°C.
(3)
Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
(4)
DC Make/Break Voltamperes must be limited to 50 VA for DC voltages between 28V dc and 125V dc. DC Make/Break
Voltamperes below 28V dc are limited by the 3 A Make/Break current limit.
IMPORTANT
Module Load Ratings
Volts (max.)
(1)
Current per relay limited to 6A at ambient temperatures above 40°C.
(2)
24A in ambient temperatures above 40°C. Limited by ambient temperature and the
number of relays controlling loads. See below.
IMPORTANT
Point
Make
(1)
5.0A
15A
(2)
30A
7.0A
0.4A
(2)
7.0A
Controller must be operated within Relay Contact Ratings (above)
and Module Load Ratings (page 13).
Controlled Load (Current) per Module (max.)
240V ac
120V ac
125V dc
24V dc
Controller must be operated within Relay Contact Ratings
(page 13) and Module Load Ratings (above).
MicroLogix™ 1200 Isolated Relay Output Module
(3)
Pilot Duty
Break
1.5A
3.0A
0.4A
3.0A
(1)
12A
(1)
12A
2.4A
(2)
30A
Publication 1762-IN017B-EN-P - March 2004
Voltamperes
Make
Break
3600 VA
360 VA
(4)
50 VA
(4)
72 VA
13