Fault messages on the display
Displayed
System characteris-
fault code
tics
F4
Burner in a fault
state
F8
Burner in a fault
state
F9
Burner in a fault
state
FA
Burner in a fault
state
FC
Burner blocked
(cont.)
Cause
No flame signal
detected
Fuel valve closes
too late
Fan speed too low
during burner start
Fan not at stand-
still
Electrical fan con-
trol (control unit)
faulty
Troubleshooting
Measures
Check the ionisation elec-
trode and cables, check
the gas pressure, check
the gas train, ignition, igni-
tion module and conden-
sate drain.
Press "Reset" (see
page 42).
Check gas train. Check
both control paths.
Press "Reset" (see
page 42).
Check fan, fan connecting
cables and power supply;
check fan control.
Press "Reset" (see
page 42).
Check fan, fan connecting
cables and fan control.
Press "Reset" (see
page 42).
Check fan connecting
cable; if required, replace
or replace control unit