Viessmann VITODENS 100-W Installation And Service Instructions Manual page 26

Type bpja
Hide thumbs Also See for VITODENS 100-W:
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Further details regarding the individual steps
A
1. Close the gas shut-off valve.
2. Undo screw A inside test nipple
"IN" on the gas train but do not
remove it, and connect the pressure
gauge.
3. Open the gas shut-off valve.
4. Check the static pressure.
Set value: max. 57.5 mbar
5. Start the boiler.
Note
During commissioning, the boiler can
enter a fault state because of airlocks
in the gas line. After approx. 5 s press
RESET to reset the burner.
26
(cont.)
6. Check the supply (flow) pressure.
Set value:
■ Natural gas: 20 mbar
■ LPG: 37 mbar
Note
Use a suitable measuring device with
a resolution of at least 0.1 mbar to
check the supply pressure.
7. Record the actual value in the report
on page.
Take the action shown in the follow-
ing table.
8. Shut down the boiler, close the gas
shut-off valve, remove the pressure
gauge and close test nipple A with
the screw.
9. Open the gas shut-off valve and start
the appliance.
Danger
Gas escaping from the test
nipple leads to a risk of explo-
sion.
Check gas tightness at test
nipple A.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents