Point Database; Overview - Siemens BACNET 125-5037 Owner's Manual

Building technologies bacnet vav actuator
Table of Contents

Advertisement

3

Point Database

Overview

Chapter 3 presents a description of the BACnet VAV Controller — Electronic Output point
database, including point descriptors, point addresses, and a listing of applications in which
each point is found.
Descriptor
Address
CTLR ADDRESS
APPLICATION
RMTMP OFFSET
ROOM TEMP
HEAT.COOL
DAY CLG STPT
NGT CLG STPT
DAY HTG STPT
NGT HTG STPT
RM STPT MIN
Siemens Building Technologies, Inc.
1
Application
01
All
02
All
03
All
2
{04}
All
{05}
All except
2560, 2597
06
All except 2597
08
All except 2597
07
All except 2560,
2597
09
All except 2560,
2597
11
All except 2597
Description
Identifies the controller on the FLN trunk.
Identification number of the program running in the
controller.
Compensates for deviations between the value of
ROOM TEMP and the actual room temperature.
This corrected value is displayed in CTL TEMP.
RMTMP OFFSET + ROOM TEMP = CTL TEMP
Actual reading from the room temperature sensor.
Current mode of operation for applications that can
be in either a heating mode or a cooling mode.
The temperature setpoint in degrees that the
controller maintains during day periods in cooling
mode if a room temperature sensor setpoint dial is
not present or is not used. See STPT DIAL.
The temperature setpoint in degrees that the
controller maintains during the night periods in
cooling mode.
The temperature setpoint in degrees that the
controller maintains during day periods in heating
mode if a room temperature sensor setpoint dial is
not present or is not used. See STPT DIAL.
The temperature setpoint in degrees that the
controller maintains during the night periods in
heating mode.
The minimum temperature setpoint in degrees that
the controller can use from the setpoint dial. This
overrides any temperature setpoint from the
setpoint dial that falls below this minimum.
20