Shortly after placement, the module will set up a connection with the calcula-
tor unit via the optical interface and read out the device information from the
meter.
Successful connection is displayed on the meter as follows:
Change between S-mode and C-mode
To change the modes, you need HMA suite, a PC and the infrared communi-
cation head WFZ.IRDA-USB.
Device information read out
• Current consumption value
• Due date value
• Due date
Device replacement
Meter replacement
• Log off the meter to be replaced from the network
• Carry out device replacement
• Log on the new meter in the network
Replacing the add-on radio module
When replacing the add-on radio module, the network node must not be repro-
grammed. The device number transmitted is read out of the calculator unit and
transmitted to the network node by the new module as before.
If ERROR 03 appears, the add-on module had been paired with another
metering device before. Proceed as described under "Error messages with
module in place".
Radio parameters
Radio frequency
Transmission power
V2.0 / 21.12.17
"FA [software version]"
"FS" = Identifier for S-mode
"FC" = Identifier for C-mode
• 13 monthly values
• Device status
• Device status
S-mode (868.30 +/- 0.30) MHz
C-mode (868.95 +/- 0.25) MHz
max. 10 dBm
MU2H-0491ge23 R1217
35