MASTER SETTINGS PROGRAMMING
continued
• language
• units
• hardness units
NOTE: Degree hardness units are converted to ppm upon
input. Degree inputs may be rounded up or down
to the nearest ppm equivalent.
USB Connection for Field Programming
NOTE: Field Programmer software is required for field
programming features. See XTR2 Field Programmer
Manual for more information on using the Field
Programmer software.
NOTE: Do not remove USB cable from computer or control
while connected and transferring data. See the XTR2
Field Programmer manual for proper disconnection
procedure.
FLECK
Valve Screen
valve
• system
• valve
• regen type
Regeneration Types
Time Clock
Softener Immediate
When setting the system for softener immediate
CAUTION
regeneration, setting the capacity to a value lower
than that of feed water hardness may cause the
system to constantly regenerate. If this occurs,
disconnect the motor from the control and correct
the capacity and feed water hardness values in
Master Settings.
Softener Delayed