Step 3: Validate The 857 Installation; Configuring The Protection System - Allen-Bradley 857 Quick Start Manual

Protection system for feeder and motor protection
Hide thumbs Also See for 857:
Table of Contents

Advertisement

Chapter 4
Installation
Step 3: Validate the 857
Installation
30
Table 15 - Typical Feeder Protection Applications
Feeder ID
Full Load Current
Current Transformer Primary
Current Transformer Secondary amps
Voltage Transformer Primary Voltage
Voltage Transformer Secondary Voltage
Ground Fault CT Primary amps
Ground Fault CT Secondary amps
1. Thoroughly inspect each of your Protection System installations before
power is applied for the first time, especially if you did not personally
perform the installation tasks.
2. Verify that each Protection System is ready to be energized before you
get to Step 4: Power Up, Configuring the Protection System and
Verifying Operation.
3. Identify which Protection System you have.
There are some important differences between Protection System
products that must be considered in subsequent steps. To determine
what type of Protection System you have, use the configuration menu
from the front of the Protection System to look under Device Info sub
menu.
4. Evaluate and note the appropriate protective elements in each
Protection System and the setting values for each specific load and
application.
See
Table 1 on page 8
5. Visually inspect the wiring connections to each Protection System.
Verify that the correct wires are connected to the appropriate input and
output terminals.
See
Measuring and Control Connections on page 15
these connections are made.
6. Apply the AC or DC power source to terminals 17 and 18 on the X3
terminal block on the left rear of the Protection System.
Protection System
Configuring the
To configure the Protection System, you must determine which inputs and
output relays are to be used within the system control circuit. Typically there
are a total of nine output relays, which are used as Trip or Alarm contacts. The
number of digital inputs vary by model type.
Rockwell Automation Publication 857-QS001B-EN-P - April 2017
Feeder 8
For example, 73 A
100
5
4160
120
100
1
for available protective elements.